EasyManua.ls Logo

YASKAWA FSDrive-MV1S - Page 217

YASKAWA FSDrive-MV1S
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FSDrive-MV1S Standard Specifications
9-3
6 kV Class Models
Note 1. FSDrive-MV1S does not have regenerative braking function.
2. Models with 10-kV input option are also available.
* 1. Maximum applicable capacity of Yaskawa’s 4-pole standard motors
* 2. An uninterruptible input power supply unit (optional) for the control power supply is required to use the restart function for momentary power loss.
Table 9.2 6 kV Class FSDrive-MV1S Standard Specifications
Model CIMR-MV1SC 250 400 630 900 13C 18C 25C 36C 50C
Max. Applicable Motor Capacity (kW)
*1
250 400 630 900 1250 1800 2500 3600 5000
Output Rating
Nominal Capacity (kVA) 400 560 800 1200 1600 2300 3000 4600 6000
Rated Output Current (A)
35
(30)
50
(45)
70
(60)
100
(85)
140
(120)
200
(170)
260
(230)
400
(350)
520
(440)
Rated Output Voltage Three-phase 6000/6600 V (sine wave)
Max. Output Frequency 50/60 Hz
Power Supply
Main Circuit (Input Voltage) Three-phase 6000/6600 V ±10%
Control Circuit
Three-phase 200/220 V, 380 V, 400/440 V ±10%
50/60 Hz ±5%
Inverter Efficiency Approx. 97% (at motor rated speed and 100% load)
Inverter Power Factor 0.95 min. (at motor rated speed and 100% load)
Cooling Method Forced air-cooling method
Control Specifica-
tions
Control Method Open-loop vector control, flux vector control
Main Circuit Voltage type series multiplex
Frequency Control Range 0.01 to 120 Hz
Frequency Control Accuracy ±0.5%
Analog Input Resolution 0.03 Hz
Overload Capacity
120% for 60 seconds (when used with above-mentioned rated
output current in the parentheses)
Acceleration/Deceleration Time 0.1 to 6,000 seconds
Main Control Functions
Restart after momentary power loss
*2
, torque limit, coasting to a
stop, jump frequencies, S-curve acceleration/deceleration, multi-
step speed control, KEB function, etc.
Protective Functions
Overcurrent, overvoltage, undervoltage, output ground fault, out-
put open-phase, overload, motor overheat, cooling fan fault, etc.
Communications Functions MODBUS, etc.
Maintainability
Control Panel
Status display, fault display, setting/reading of commands and
constants
Main Circuit Module configuration
Environmental
Specifications
Enclosure IP 40
Ambient Temperature and Humidity -5 to +40°C, 85%RH max. (with no condensation)
Storage Temperature 0 to +50°C
Atmosphere
General environmental conditions (free from dust or corrosive
gas), altitude: 1,000 m max.
General Specifica-
tions
Paint Color
Internal and external surface painted in Munsell 5Y/7/1 semi-
glossy
Applicable Standards JIS, JEC, JEM, Electric Facility Technical Reference

Table of Contents

Related product manuals