Trial Operation Procedures
4-5
* The factory settings depend on the Inverter capacity.
Control Method Settings
Autotuning methods depend on the control method set for the Inverter. Make the settings as required by the
control method used.
Control Method Selection
Either of the following two control methods can be selected.
Turning on the Medium-voltage Power Supply
Items to be checked before turning on the medium-voltage power supply:
• Confirm that the medium-voltage power supply is the correct voltage.
• Confirm that the Inverter main circuit terminals (input terminals R, S, and T and output terminals U, V, and
W) are correctly connected.
• Make sure that the motor is not connected to a mechanical system (No-load status).
Items to be checked after turning on the medium voltage power supply:
• Measure the input voltage of each power cell.
If the input voltage exceeds the power cell rated input voltage of 630 VAC, switch the transformer tap set-
ting for main circuit and recheck the input voltage.
• Use the Digital Operator to confirm input power supply voltage U1-90.
• Confirm that the Digital Operator displays the Inverter as being in normal status.
{ o2-04
FSDrive-MV1S
capacity selection
Not initialized in A1-03 (Initialize).
Code: rated voltage, kVA, kW, rated current
60: 3300V, 200 kVA, 132 kW, 35 A
61: 3300V, 285 kVA, 200 kW, 50 A
62: 3300V, 400 kVA, 315 kW, 70 A
63: 3300V, 570 kVA, 450 kW, 100 A
64: 3300V, 800 kVA, 630 kW, 140 A
65: 3300V, 1150 kVA, 900 kW, 200 A
66: 3300V, 1500 kVA, 1250 kW, 260 A
67: 3300V, 2300 kVA, 1800 kW, 400 A
68: 3300V, 3000 kVA, 2500 kW, 520 A
70: 6600V, 400 kVA, 250 kW, 35 A
71: 6600V, 570 kVA, 400 kW, 50 A
72: 6600V, 800 kVA, 630 kW, 70 A
73: 6600V, 1150 kVA, 900 kW, 100 A
74: 6600V, 1600 kVA, 1250 kW, 140 A
75: 6600V, 2300 kVA, 1800 kW, 200 A
76: 6600V, 3000 kVA, 2500 kW, 260 A
77: 6600V, 4600 kVA, 3550 kW, 400 A
78: 6600V, 6000 kVA, 5000 kW, 520 A
Usually setting is not necessary.
60 to
FFH
Code corre-
sponding to
Inverter
capacity
Control Method Constant Setting Basic Control Main Applications
Open-loop vector
control
A1-02 = 2
(Factory setting)
Current vector control
without a PG
Variable speed control that requires high performance
without using a PG
Flux vector
control
A1-02 = 3
Current vector control
with a PG
Ultra high-performance control using a PG such as
high-accuracy speed control, torque control, and torque
limit
Table 4.1 Required and Optional Constant Settings (Continued)
: Required constant settings, {: Optional constant settings
Category
Constant
Number
Name Description
Setting
Range
Factory
Setting