User Constant Tables
5-23
* 1. The factory settings depend on the Inverter capacity.
* 2. Only multiples of 2 can be set.
E2-11
Motor rated output Set the rated output of the
motor in units of 0.01 kW.
This constant is automatically
set during autotuning.
0 to
10000
630
kW
No Q Q 36AH
Mtr Rated Power
E2-12
Motor wiring resistor
Set the motor wiring resistance
in % units.
0.00 to
1.00
0.00% Yes A A 36BH
Wiring Resistor
E2-13
Motor temperature OH
level
Set the motor temperature OH
level in °C units.
50 to
200
120°C No A A 36CH
Motor Temp OHLVL
E2-14
Motor Thermistor
selection
0: Motor Thermistor disabled.
1: Motor Thermistor enabled.
0 or 1 0 No A A 36DH
Motor Thermistor
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display