5-22
Motor Setup: E2
User constants for motor 1 are shown in the following table.
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
E2-01
Motor rated current Sets the motor rated current in
1 A units.
These set values will become
the reference values for motor
protection, torque limits and
torque control.
This constant is automatically
set during autotuning.
0.1 to
1500.0
86.6 A
*1
No Q Q 360H
Motor Rated FLA
E2-02
Motor rated slip Sets the motor rated slip in Hz
units.
These set values will become
the reference values for slip
compensation.
This constant is automatically
set during autotuning.
0.00 to
20.00
0.75 Hz
*1
Yes Q Q 361H
Motor Rated Slip
E2-03
Motor no-load current Sets the motor no-load current
in 1 A units.
This constant is automatically
set during autotuning.
0.00 to
1500.0
32.2 A
*1
Yes Q Q 362H
No-Load Current
E2-04
Number of motor
poles
Sets the number of motor poles.
This constant is automatically
set during autotuning.
2 to 48
*2
6 poles No Q Q 363H
Number of Poles
E2-05
Motor line-to-line
resistance
Sets the motor phase-to-phase
resistance in units.
This constant is automatically
set during autotuning.
0.000
to
65.000
0.307
*1
Yes A A 364H
Term Resistance
E2-06
Motor leak inductance Sets the voltage drop due to
motor leakage inductance as a
percentage of the motor rated
voltage.
This constant is automatically
set during autotuning.
0.0 to
40.0
27.2%
*1
Yes A A 365H
Leak Inductance
E2-07
Motor iron saturation
coefficient 1
Sets the motor iron saturation
coefficient at 50% of magnetic
flux.
This constant is automatically
set during autotuning.
0.00 to
1.00
0.50
*1
Yes A A 366H
Saturation Comp1
E2-08
Motor iron saturation
coefficient 2
Sets the motor iron saturation
coefficient at 75% of magnetic
flux.
This constant is automatically
set during autotuning.
0.00 to
1.00
0.75
*1
Yes A A 367H
Saturation Comp2
E2-09
Motor mechanical loss
Sets motor mechanical loss as a
percentage of motor rated out-
put (W).
Usually setting is not necessary.
Adjust in the following circum-
stances:
When torque loss is large
due to motor bearing.
When the torque loss in the
pump or fan is large.
The set mechanical loss will
compensate for torque.
0.0 to
10.0
0.0% Yes No A 368H
Mechanical Loss