User Constant Tables
5-47
o2-05
Frequency
reference setting
method selection
When the frequency reference is
set on the Digital Operator fre-
quency reference monitor, sets
whether the Enter Key is necessary.
0: Enter Key needed
1: Enter Key not needed
When set to 1, the Inverter accepts
the frequency reference without
Enter Key operation.
0 or 1 0 No A A 6F4H
Operator M.O.P.
o2-06
Operation selection
when digital opera-
tor is disconnected
Sets the operation when the Digital
Operator is disconnected.
0: Disabled (Operation continues
even if the Digital Operator is
disconnected.)
1: Enabled (OPR is detected at
Digital Operator disconnection.
Inverter output is cut off, and
fault contact is operated.)
0 or 1 0 No A A 6F5H
Oper Detection
o2-07
Cumulative opera-
tion time setting
Sets the cumulative operation time
in hour units.
Operation time is calculated from
the set values.
0 to
65535
0 hr No A A 6F6H
Elapsed Time Set
o2-08
Cumulative opera-
tion time selection
0: Cumulative time when the
Inverter power is on. (All time
while the Inverter power is on is
accumulated.)
1: Cumulative Inverter run time.
(Only Inverter output time is
accumulated.)
0 or 1 0 No A A 6F7H
Elapsed Time Run
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display