Machine Protection
6-29
Multi-function Output (H2-01 to H2-08)
L6-03
Overtorque/
Undertorque detection
time 1
Sets the overtorque/under-
torque detection time in 1-sec-
ond units.
0.0 to
10.0
0.1 s No A A 552H
Torq Det 1 Time
L6-04
Overtorque/Under-
torque
detection selection 2 Multi-function output for over-
torque detection 1 is output to
multi-function contact output
when overtorque detection 1
NO or overtorque detection 1
NC is selected. Multi-function
output for overtorque detection
2 is output to multi-function
contact output when overtorque
detection 2 NO or overtorque
detection 2 NC is selected.
0 to 8 0 No A A 553H
Torq Det 2 Sel
L6-05
Overtorque/Under-
torque
detection level 2
0 to
300
150% No A A 554H
Torq Det 2 Lvl
L6-06
Overtorque/Under-
torque
detection time 2
0.0 to
10.0
0.1 s No A A 555H
Torq Det 2 Time
Setting
Value
Function
Control Methods
Open-
loop
Vector
Flux
Vector
B Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque detection at on) Yes Yes
17 Overtorque/undertorque detection 1 NC (NC Contact: Overtorque/undertorque detection at off) Yes Yes
18 Overtorque/undertorque detection 2 NO (NO Contact: Overtorque/undertorque detection at on) Yes Yes
19 Overtorque/undertorque detection 2 NC (NC Contact: Overtorque/undertorque detection at off) Yes Yes
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display