6-38
b3-12
Current detection
dead-zone width
during speed search
On speed calculation, the motor
speed is calculated from the
detected current value. For cur-
rent detection, the dead-zone
must be set. Set the dead-zone
width using the current detec-
tion resolution as reference
amount. (only for a excitation
search)
Decrease the set value if the
search speed becomes
extremely slow at the speed
search after the motor has been
baseblocked for a long time of
period such as the speed search
at startup.
0.5 to
10.0
4.0 No A A 1CBH
Srch I Deadband
b3-13
Torque compensation
time constant during
speed search
Sets primary lag of the torque
compensation function during
speed search in units of milli-
seconds.
0 to
10000
10 ms No A A 1CCH
TComp T at SpdSr
b3-14
Current control start
level during voltage
restoration
Sets the level to start prolonga-
tion of voltage restoration time
to control current during speed
search. Set the level as no-load
current = 1.0.
0.0 to
5.0
2.0 No A A 1CDH
Srch Lvl Red I
b3-15
Time constant for
current control during
voltage restoration
Sets the time constant for filter-
ing for the level to prolong
voltage restoration time in
order to control current during
speed search.
0 to
100
5 ms No AA1CEH
Srch T Red I
b3-16
Wait time after
completion of speed
search
Sets the wait time for switching
to normal control after comple-
tion of speed search. The fre-
quency reference will be held
during the set wait time.
0.00 to
5.00
0.01 s No A No 1CFH
SpdSrch Ret Time
b3-17
Software CLA current
limit 1 during speed
search
Sets the software current limit
value at speed search in per-
centage to the motor rated cur-
rent.
0.0 to
300.0
100.0% No A A 1D0H
SpdSrch CLA Lvl1
b3-18
Software CLA current
limit 2 during speed
search
Sets the software current limit
value at 0 Hz at speed search in
percentage to the motor rated
current.
0.0 to
300.0
100.0% No A A 1D1H
SpdSrch CLA Lvl2
L2-03
Min. baseblock time Sets the Inverter's minimum
baseblock time in units of one
second, when the Inverter is
restarted after power loss ride-
through.
Sets the time to approximately
0.7 times the motor secondary
circuit time constant.
When an overcurrent or over-
voltage occurs when starting a
speed search or DC injection
braking, increase the set values.
0.1 to
5.0
2.0 s
*2
No A A 4F2H
PwrL Baseblock t
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display