Continuing Operation
6-41
Speed Search after Short Baseblock (during Power Loss Recovery, etc.)
The time chart when the Inverter operation is restarted after power has been restored is shown below.
Loss Time Shorter Than the Minimum Baseblock Time (L2-03)
Fig 6.16 Speed Search after Baseblock (When Estimated Speed: Loss Time Is Set in L2-03)
Loss Time Longer Than the Minimum Baseblock Time (L2-03)
Fig 6.17 Speed Search After Baseblock (Estimated Speed: Loss Time > L2-03)
Main circuit
power supply
Output frequency
Output current
Off
On
Start using
speed detected
Set frequency
reference
Minimum baseblock time (L2-03) x 0.75*1
10 ms
*1 Baseblock time may be reduced by the output frequency
immediately before the baseblock.
*2 After Main circuit power supply recovery, motor waits for th
e
minimum Speed Search Wait Time (b3-05).
*2
Main circuit
power supply
Output frequency
Output current
Off
On
Start using speed detected
Set frequency
reference
Minimum baseblock time
(L2-03)
10 ms
Speed Search Wait Time
(b3-05)