Protective and Diagnostic Functions
7-5
CF
Out of Control
F
Control Fault
The torque limit was reached continuously
for 3 seconds or longer during a deceleration
stop during open-loop vector control.
Check the motor constants.
Constant: E1-, E2-
Lengthen the deceleration time.
Constant: C1-
OPR
Opr Disconnect
F
Digital Operator Connection Fault
The connection to the Digital Operator was
broken during operation for a RUN command
from the Digital Operator.
Detected when 02-06 is set to1.
Check the connection to the Digital Oper-
ator.
CPF00
COM-ERR
(OP &INV)
F
Digital Operator Communications Error 1
Communications with the Digital Operator
were not established within 5 seconds after
the power was turned on.
Disconnect the Digital Operator and then
connect it again.
Try turning the control power supply off
and on again.
Replace the Digital Operator or the CPU
board.
CPF01
COM-ERR
(OP &INV)
F
Digital Operator Communications Error 2
After communications were established,
there was a communications error with the
Digital Operator for more than 2 seconds.
Disconnect the Digital Operator and then
connect it again.
Replace the Digital Operator or the CPU
board.
CPF03
EEPROM Error
F
EEPROM error
The control circuit is damaged.
Try turning the control power supply off
and on again.
Replace the modulator board.
CPF05
External A/D Err
F
CPU internal A/D converter error
The control circuit is damaged.
Try turning the control power supply off
and on again.
Replace the modulator board.
HDE
HARD Fault
F
Modulator board Hardware Fault
The modulator board is damaged.
Try turning the control power supply off
and on again.
Replace the modulator board.
DTM
MB Watchdog Flt
F
Modulator Watchdog Fault
The communication error between with the
modulator board and the CPU board
occurred.
Try turning the control power supply off
and on again.
Replace the CPU board or the modulator
board.
CTF
Analog Pwr Fault
F
Analog Power supply Fault
The analog power supply (±15V) was low-
ered.
Replace the analog power supply (±15V).
CER
CTL CPU Fault
F
CPU Watchdog Fault
The watchdog timeover occurred in the CPU
board.
Try turning the control power supply off
and on again.
Replace the CPU board.
BAT
Weak Battery
F
Battery Lowered
Battery for memory on the CPU board was
lowered.
Replace the battery on the CPU board.
EF x
Ext Fault Sx
F/A
External Fault (Input terminal Sx)
x = 3 to 16
An “external fault” was input from a multi-
function input terminal.
Reset external fault inputs to the multi-
function inputs.
Remove the cause of the external fault.
Table 7.1 List of Drive Faults (Continued)