User Constant Tables
5-11
b3-06
Output current 1
during speed search
Sets the output current during
the first half of speed search as
a coefficient to the motor rated
current (E2-01). (Only for exci-
tation search) Increase the set
value if the search speed
becomes extremely slow at the
speed search after the motor
has been base-blocked for a
long time of period such as the
speed search at startup.
0.0 to
1.0
0.5 No A A 1C5H
Srch Im Lvl1
b3-07
Output current 2
during speed search
Sets the output current during
the last half of speed search as a
coefficient to the motor no-load
current (E2-03). The multipli-
cation of motor no-load current
and set coefficient is limited to
the motor rated current (E2-01)
inside the Inverter. (Only for
excitation search) Increase the
set value if the search speed
becomes extremely slow at the
speed search after the motor
has been base-blocked for a
long time of period such as the
speed search at startup.
0.0 to
3.0
1.5 No A A 1C6H
Srch Im Lvl2
b3-10
Speed search detection
compensation gain
(speed calculation)
Operation restarts at a speed
obtained by multiplying the
speed from the speed search by
the compensation gain (excita-
tion search only.)
Increase this setting if overvolt-
ages of cells occur when a
speed search is performed after
a long baseblock, for example,
in searches at startup.
1.00 to
1.50
1.05 No A No 1C9H
Srch Detect Comp
b3-11
Speed search method
switching level
On speed calculation, the
search method is automatically
switched according to the
motor residential voltage. Set
the switching level.
0.5 to
100.0
5.0% No A A 1CAH
Srch Mthd Sw Lvl
b3-12
Current detection
dead-zone width
during speed search
On speed calculation, the motor
speed is calculated from the
detected current value. For cur-
rent detection, the dead-zone
must be set. Set the dead-zone
width using the current detec-
tion resolution as reference
amount. (only for a excitation
search)
Decrease the set value if the
search speed becomes
extremely slow at the speed
search after the motor has been
baseblocked for a long time of
period such as the speed search
at startup.
0.5 to
10.0
4.0 No A A 1CBH
Srch I Deadband
b3-13
Torque compensation
time constant during
speed search
Sets primary lag of the torque
compensation function during
speed search in units of milli-
seconds.
0 to
10000
10 ms No A A 1CCH
TComp T at SpdSr
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display