User Constant Tables
5-27
Multi-function Contact Input Functions
Note Set to 0F when contact input is used for the built-in PLC or not used as multi-function contact input.
Setting
Value
Function
Control Methods
Open-
loop
Vector
Flux
Vector
00 3-wire sequences (Forward/Reverse Run Command) Yes Yes
01 Local/Remote selection (on: Operator, off: Constant setting) Yes Yes
02 Option/Inverter selection (on: Option board) Yes Yes
03
Multi-step speed reference 1
When H3-09 (Multi-function analog input function selection) is set to 0 [Auxiliary frequency
(speed) reference], this function is combined with the master/auxiliary speed switch.
Yes Yes
04 Multi-step reference 2 Yes Yes
05 Multi-step reference 3 Yes Yes
06 Jog frequency command (higher priority than multi-step speed reference) Yes Yes
07 Accel/decel time 1 Yes Yes
08 External baseblock NO (NO contact: Baseblock at on) Yes Yes
09 External baseblock NC (NC contact: Baseblock at off) Yes Yes
0A Acceleration/deceleration ramp hold (on: Acceleration/deceleration stopped, frequency on hold) Yes Yes
0B OH2 alarm signal input (on: OH2 will be displayed) Yes Yes
0C Multi-function analog input selection (on: Enable) Yes Yes
0E Speed control integral reset (on: Integral control disabled) No Yes
0F Not used (Set when the terminal is used for the built-in PLC or not used.) Yes Yes
10 Up command (Always set with the down command.) Yes Yes
11 Down command (Always set with the up command.) Yes Yes
12 FJOG command (on: Forward run at jog frequency (d1-17)) Yes Yes
13 RJOG command (on: Reverse run at jog frequency (d1-17)) Yes Yes
14 Fault reset (Reset when turned on.) Yes Yes
18
Timer function input [Functions are set in B4-01 and B4-02. Set with timer function output
(multi-function output).]
Yes Yes
1A Accel/decel time 2 Yes Yes
1B
Constants write enable (on: All constants can be written-in. off: All constants other than speed
monitor are write prohibited.)
Yes Yes
1E Analog frequency reference sample/hold Yes Yes
1F Frequency reference terminal AI0/AI1 selection (on: AI1) Yes Yes
20 to 2F
External fault (Desired settings possible) Input mode: NO contact/NC contact, Detection mode:
Normal/during operation, Stopping method: Deceleration to a stop/coast to a stop/ emergency
stop/ continues running
Yes Yes
60 DC injection braking command (on: Performs DC injection braking) Yes Yes
61 External speed search command 1 (on: Speed search from maximum output frequency) Yes No
62 External speed search command 2 (on: Speed search from set frequency) Yes No
6F Emergency stop (NO contact: Coast to a stop when on) Yes Yes
70 Emergency stop (NC contact: Coast to a stop when off) Yes Yes
71 Speed/torque control change (on: Torque control) No Yes
77
Speed control (ASR) proportional gain switch (on: C5-03, off: Gain determined by C5-01, C5-
03, and C5-09)
No Yes