Table 4.11 “L” Parameters
Access Level
Name
Address Description Data
Range Unit Default
During
Run
V/f
V/f
w/PG
OLV
FV OLV2
2 2/3 Phase Loss Detection
0 Disabled
L8-09
04B5h
Ground Fault (GF)
Selection
1 Enabled
1 1 A A A A A
0 Fan On Only During Run
L8-10
04B6h
Cooling Fan On/Off
Selection
1 Fan Always On
1 0 A A A A A
L8-11
04B7h
Fan Off Delay Time
After Stop Command
0 ~ 300 Sec 1 Sec 60 Sec A A A A A
L8-12
04B8h Ambient Temperature 45 ~ 60 Deg 1 Deg 45 Deg A A A A A
0 Disabled
L8-15
04BBh
Inverter Overload (OL2)
Selection at Low Speed
1 Enabled
1 1 A A A A A
0 Disabled
L8-18
04BEh
Software CLA Selection
(150% Current Limit)
1 Enabled
1 1 A A A A A
0 Disabled
L8-33
04E3h
Control Fault 2 (CF2)
Selection
1 Enabled
1 1 A

Other manuals for YASKAWA G7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 and is the answer not in the manual?

YASKAWA G7 Specifications

General IconGeneral
TypeDC Drive
Enclosure RatingIP20
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Communication InterfaceRS-485
Humidity5 to 95% (non-condensing)
Storage Temperature-20°C to 60°C (-4°F to 140°F)

Related product manuals