29
No Response
The slave disregards the command message and does not return a response message in the following cases:
1. In broadcasting of data (slave address is 0), all slaves execute, but do not respond.
2. When a communication error (overrun, framing, parity, or CRC-16) is detected in the command message.
3. When the slave address in the command message does not coincide with the address set in the slave.
4. When it takes longer than 2 seconds to send a message.
5. When the time interval between characters exceeds 3.5 ms.
6. When the command message data length is not proper.
Error Codes
Table 2.14 Fault Codes
Code Fault Description
1 Function Error Invalid or unsupported function code in command message
2 Invalid Register Invalid register address
3 Invalid Number of Registers Invalid command message quantity
21 Data Limits Exceeded The write command message data is out of range for the requested register
22 Write Failure The register to be written is write protected

Other manuals for YASKAWA G7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA G7 and is the answer not in the manual?

YASKAWA G7 Specifications

General IconGeneral
TypeDC Drive
Enclosure RatingIP20
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Communication InterfaceRS-485
Humidity5 to 95% (non-condensing)
Storage Temperature-20°C to 60°C (-4°F to 140°F)

Related product manuals