EasyManua.ls Logo

YASKAWA iQpump Micro

YASKAWA iQpump Micro
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
YASKAWA TOEP YAIQPM 01A iQpump Micro Quick Start Procedure
iQpump Micro
Quick Start Procedure
Page 22
of 31
Task Parameter Name Description/Menu Access Default Value
8.7 Program the Start Level as an Absolute
Value.
Start / Draw Down Level must be
programmed to a positive value for the Start /
Draw Down Level to be an absolute value.
Example: Start / Draw Down Level P1-04 set
to 50 PSI and delay time P1-05 set to 5 sec.
Result: Pump system will start when the
pressure drops below 50 PSI for 5 sec.
Important! It is mandatory to program the Start / Draw Down Level in order to
use the sleep function.
OR
Program the Start Level as a Delta Level
from the System Setpoint
Start / Draw Down Level must be
programmed to a negative value for the Start
Level to be a delta value from the setpoint.
Example: Start / Draw Down Level P1-04 set
to –10 PSI with a system setpoint of 50 PSI
and delay time P1-05 set to 5 sec.
Result: Pump system will start when the
pressure drops below 40 PSI (50 - 10) for 5
sec.
8.8 Set Minimum Pump
Frequency to the value at
which the pump enters a no-
ow condition.
P1-06 Minimum Pump
Speed
Minimum speed (Hz) for pump motor
operation.
40.0 Hz
8.9 Recommended for use
when the Start/Stop command
is from the digital operator
WARNING! Sudden Movement
Hazard. If the drive is powered
down while running, it will
automatically initiate an internal
Run command upon power-up.
P4-10 AUTO Mode Operator
Run Power Down
Storage
Stores the run status in the AUTO mode
when operating from digital operator (b1-
02=0).
0: Disabled
1: Enabled
0: Disabled
Optional step: HAND key on
digital operator.
P5-04 HAND Key Function
Selection
Enables or disables the HAND key on the
digital operator.
0: Disabled
1: Enabled
1: Enabled
Parameter Overview-Quick Setting Menu (Simplex) continued.