YASKAWA TOEP YAIQPM 01A iQpump Micro Quick Start Procedure
iQpump Micro
Quick Start Procedure
Page 27
of 31
12.1 AUTO Mode
The iQpump Micro is operated in AUTO mode by performing the following tasks: Program all parameters
Verify motor rotation direction
Auto Mode: Select the Reference source setting in parameter b1-01
Auto Mode: Select the Run source setting in parameter b1-02 (Refer to STEP 4)
LED Digital Operator (Standard)
Press the AUTO button to place the iQpump Micro into AUTO mode
.
The AUTO mode will start and stop based on the Run Source Selection setting parameter b1-02. (Refer to Step 3) The
Reference Source Selection parameter b1-01 setting configures the AUTO mode reference source.
Figure 4: Digital Operator
LED is blinking
when AUTO mode
is active but AUTO
Run Command is
not active.
SETPOINT
PRESS AUTO BUTTON
PRESS TO TURN OFF
5 80.0
12.2 Set System Setpoint
LED Digital Operator (Standard)
Press
to access or modify the system setpoint in parameter Q1-01 within the iQpump Micro Quick Setup Menu.
The iQpump Micro starts in AUTO Mode when the feedback signal level falls below the level programmed in parameter
P1-04 for the specified time in P1-05.
Use
to select the digit and
Next press
Press the AUTO button to
start the iQpump Micro.
Start Pump System
Start
Delay
145 PSI
Start / Draw Down
Level P1-04
System Setpoint
(Example 80 PSI)
Feedback signal from
pressure transducer
(4 – 20 mA)
0
Pressure
Start Level Delay (P1-05)
(Example 5.0 sec.)
WAIT
to store setpoint.
Refer to STEP 8,
parameter P1-04 for
details on the Start
Level Function.
iQpump Micro Quick Setup Menu.
Example: 80 PSI
. Next press
to store setpoint.
5 80.0
5 80.0
AUTO Mode Operation
12
STEP