YASKAWA TM.iQp.02 iQpump Drive Programming Manual 185
H4-04 0420H
Terminal AM Monitor
Selection
Ter minal AM Se l
Selects which monitor will be output on terminals AM and AC.
1: Frequency Ref (100% = max. output frequency)
2: Output Freq (100% = max. output frequency)
3: Output Current (100% = Drive rated current)
6: Output Voltage (100% = 230 V or 100% = 460 V)
7: DC Bus Voltage (100% = 400 V or 100% = 800 V)
8: Output kWatts (100% = Drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100% = Motor rated secondary current)
20: SFS Output (100% = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Setpoint
Note: 100% = 10 V DC output * AM gain setting (H4-05).
1 to 38
<0032>
8Programming79
H4-05
0421H
Terminal AM Gain
Setting
Terminal AM Gain
Sets terminal AM output voltage (in percent of 10 V) when selected
monitor is at 100% output.
0.0 to
1000.0
50.0% Programming
79
H4-06
0422H
Terminal AM Bias
Setting
Ter minal AM Bi as
Sets terminal AM output voltage (in percent of 10 V) when selected
monitor is at 0% output.
–110.0 to
110.0
0.0% Programming
79
H4-07 0423H
Terminal FM Signal
Level Selection
AO Level Select1
0: 0 - 10 Vdc
2: 4-20 mA*
0 or 2 0 Programming
80
H4-08 0424H
Terminal AM Signal
Level Selection
AO Level Select2
0: 0 - 10 Vdc
2: 4-20 mA*
* An analog output of 4 - 20 mA cannot be used with the standard
terminal board. Therefore an optional terminal board (with shunt
connector CN15) is needed.
0 or 2 0 Programming
80
Denotes that parameter can be changed when the drive is running.
Serial Com Setup
H5-01 0425H
Drive Node Address
Serial Com Adr
Selects Drive station node number (address) for terminals R+, R-, S+,
S-.*
Note: An address of “0” disables serial com.
0 to 20
(H5-08=0)
0 to FF
(H5-08=1)
0 to 63
(H5-08=2)
1F Programming
93
H5-02 0426H
Communication Speed
Selection
Serial Baud Rate
Selects the baud rate for terminals R+, R-, S+ and S-.*
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud
0 to 4 3 Programming
93
H5-03 0427H
Communication Parity
Selection
Serial Com Sel
Selects the communication parity for terminals R+, R-, S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity
0 to 2 0 Programming
93
H5-04 0428H
Stopping Method after
Communication Error
Serial Fault Sel
Selects the stopping method when a communication error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0 to 3 3 Programming
94
H5-05 0429H
Communication Error
Detection Selection
Serial Flt Dtct
Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a
communications fault.
1: Enabled - If communications are lost for more than the time
specified in parameter H5-09, a communications fault will occur.
0 or 1 1 Programming
94
H5-06 042AH
Drive Transmit Wait
Time
Transmit WaitTIM
Sets the time from when the Drive receives data to when the Drive
sends data.
5 to 65 5 ms Programming
94
H5-07 042BH
RTS Control Selection
RTS Control Sel
Enables or disables “request to send” (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)
0 or 1 1 Programming
94
Parameter
No.
Modbus
Address
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.