B Parameter Table
184 YASK AWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
9 Speed Reference Source
Open: The speed reference is supplied by an external reference (set in b1-01).
Closed: Digital operator supplies the speed reference.
A Up/Down Command Source
Open: The Up/Down command is supplied by an external reference (set in b1-02).
Closed: Digital operator supplies the Up/Down command.
B Torque Detection 1
Closed: An overtorque or undertorque situation has been detected.
EFault
Closed: Fault occurred. (excluding CPF00 and CPF01)
F Not used (Through Mode)
Set this value when the terminal is not used or when using the terminal in the pass-through mode.
10 Minor Fault
Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected life span.
11 Fault Reset Command Active
Closed: The drive has received a reset command from the multi-function input terminals or from
serial network, or the digital operator’s RESET key has been pressed.
12 Timer Output
Closed: Timer output.
13 Speed Agree 2
Closed: When drive output frequency equals the speed reference ±L4-04.
14 User-set Speed Agree 2
Closed: When the drive output speed is equal to the value in L4-03 ±L4-04.
15 Speed Detection 3
Closed: When the drive output speed is less than or equal to the value in L4-03 ±L4-04.
16 Speed Detection 4
Closed: When the output speed is greater than or equal to the value in L4-03 ±L4-04.
18 Torque Detection 2
Closed: Overtorque or undertorque has been detected.
1A During Down Direction
Closed: Drive is running in the down direction.
1B During Baseblock 2 (N.C.)
Open: Drive has entered the baseblock state (no output voltage).
1C Motor 2 Selection
Open: Motor 1 is selected
Closed: Motor 2 is selected
1D During Regeneration
Closed: Motor is operated in regenerative mode.
1E Reset Enabled
Closed: An automatic reset is performed
1F Motor Overload Alarm (oL1)
Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.
H2 Multi-Function Digital Output Settings
H2-
Setting
Function Description
All Modes
All Modes
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV