2.5 Selecting Peripheral Devices
2-25
2.5.2 Molded-case Circuit Breaker and Fuse Capacity
* 1. Nominal value at the rated load. The specified derating is required to select an appropriate
fuse capacity.
* 2. Cutoff characteristics (25°C): 200% two seconds min. and 700% 0.01 seconds min.
Note: Do not use a fast-acting fuse. Because the SERVOPACK’s power supply is a capacitor
input type, a fast-acting fuse may blow when the power is turned ON.
The SGDS SERVOPACK does not include a protective grounding circuit. Install a ground-fault protector to
protect the system against overload and short-circuit or protective grounding combined with the molded-
case circuit breaker.
Main Circuit
Power Supply
Servo Amp. Model
Power Supply Capacity
per Servo Amplifier
(kVA)
Current Capacity of
Molded-case Circuit Breaker or Fuse
(A
rms
)
*1,*2
(Refer to 4.4.5)
Capacity
(kW)
SGDS
-
Single-phase
100 V
0.05 A5F 0.25
4
0.10 01F 0.40
0.20 02F 0.60 6
0.40 04F 1.2 12
Single-phase
200 V
0.05 A5A 0.25
40.10 01A 0.40
0.20 02A 0.75
0.40 04A 1.2 8
0.80 08A 2.2 16
Three-phase
200 V
0.45 05A 1.4 4
1.0 10A 2.3 7
1.5 15A 3.2 10
2.0 20A 4.3 12
3.0 30A 5.9 17