5 Installation Procedure
22 YASKAWA ELECTRIC TOBP C730600 60C V1000 Option SI-EN3/V Installation Manual
4.
On IP20/Open-Chassis models, connect the drive side of the ground wire to the
drive ground terminal.
Note: The four different ground wires packaged with the option connect the option to different drive
models. Select the proper ground wire depending on drive size. Refer to Table 7 for ground wire
selection by drive model.
Figure 7
Figure 7 Connect the Ground Wire on an IP20/Open-Chassis Drive
Table 7 Ground Wire Selection
Ground Wire
Length
(mm/in)
Drive Model
CIMR-V
Single-Phase
200 V Class
Three-Phase
200 V Class
Three-Phase
400 V Class
150/5.9
BA0001
BA0002
BA0003
2A0001
2A0002
2A0004
2A0006
–
200/7.9
BA0006
BA0010
BA0012
BA0018
2A0010
2A0012
2A0020
4A0001
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
250/9.8 –
2A0030
2A0040
4A0018
4A0023
400/15.7 –
2A0056
2A0069
4A0031
4A0038
Ground terminal
Ground wire
Ground wire
Drive-side
connector
Screw size:
M3.5 to M6
Option unit
connector
Screw size: M3