EasyManua.ls Logo

YASKAWA Varispeed CIMR-G7A - Reference Constants: D

YASKAWA Varispeed CIMR-G7A
459 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Constant Tables
5-27
Reference Constants: d
The following settings are made with the reference constants (d constants): Frequency references.
Preset Reference: d1
User constants for frequency references are shown in the following table.
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
d1-01
Frequency
reference 1
Sets the frequency reference
in the units used in o1-03.
0 to
400.00
*
0.00 Hz Yes Q Q Q Q Q 280H
4-6
6-5
Reference 1
d1-02
Frequency
reference 2
The frequency reference
when multi-step speed refer-
ence 1 is ON for a multi-func-
tion input.
0.00 Hz Yes Q Q Q Q Q 281H
4-6
6-5
Reference 2
d1-03
Frequency
reference 3
The frequency reference
when multi-step speed refer-
ence 2 is ON for a multi-func-
tion input.
0.00 Hz Yes Q Q Q Q Q 282H
4-6
6-5
Reference 3
d1-04
Frequency
reference 4
The frequency reference
when multi-step speed refer-
ences 1 and 2 are ON for
multi-function inputs.
0.00 Hz Yes Q Q Q Q Q 283H
4-6
6-5
Reference 4
d1-05
Frequency
reference 5
The frequency when multi-
step speed reference 3 is ON
for a multi-function input.
0.00 Hz Yes A A A A A 284H 6-5
Reference 5
d1-06
Frequency
reference 6
The frequency reference
when multi-step speed refer-
ences 1 and 3 are ON for
multi-function inputs.
0.00 Hz Yes A A A A A 285H 6-5
Reference 6
d1-07
Frequency
reference 7
The frequency reference
when multi-step speed refer-
ences 2 and 3 are ON for
multi-function inputs.
0.00 Hz Yes A A A A A 286H 6-5
Reference 7
d1-08
Frequency
reference 8
The frequency reference
when multi-step speed refer-
ences 1, 2, and 3 are ON for
multi-function inputs.
0.00 Hz Yes A A A A A 287H 6-5
Reference 8
d1-09
Frequency
reference 9
The frequency reference
when multi-step speed refer-
ence 4 is ON for a multi-func-
tion input.
0.00 Hz Yes A A A A A 288H -
Reference 9
d1-10
Frequency
reference 10
The frequency reference
when multi-step speed refer-
ences 1 and 4 are ON for
multi-function inputs.
0.00 Hz Yes A A A A A 28BH -
Reference 10
d1-11
Frequency
reference 11
The frequency reference
when multi-step speed refer-
ences 2 and 4 are ON for a
multi-function inputs.
0.00 Hz Yes A A A A A 28CH -
Reference 11

Table of Contents

Related product manuals