5-76
îš‹ T: Motor Autotuning
The following settings are made with the motor autotuning constants (T constants): Settings for autotuning.
* 1. Set T1-02 and T1-04 when 2 is set for T1-01. Only set value 2 is possible for V/f control or V/f control with PG.
* 2. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 3. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter for 0.4 kW is given.
* 4. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
* 5. Applicable for Control Boards ETC618046-S1033 and later. Refer to Chapter 8 Procedure for Adjusting Constants after Replacement of Control
Board (Page 8-3) for the details of setting 3 (Shipping adjustment).
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
T1-00
Motor 1/2
selection
Set the location where the
autotuned motor constants are
to be stored.
1: Motor 1
2: Motor 2
1 or 2 1 No Yes Yes Yes Yes Yes 700H 4-13
Select Motor
T1-01
Autotuning
mode selec-
tion
Set the autotuning mode.
0: Rotational autotuning
1: Stationary autotuning
2: Stationary autotuning for
line-to-line resistance
only
3: Shipping adjustment
0 to 2
*1
0 No Yes Yes Yes Yes Yes 7 01H
4-10
4-13
Tuning Mode
Sel
0 to 3
*1
*5
T1-02
Motor output
power
Set the output power of the
motor in kilowatts.
0.00 to
650.00
0.40
kW
No Yes Yes Yes Yes Yes 702H 4-13
Mtr Rated
Power
T1-03
Motor rated
voltage
Set the rated voltage of the
motor in volts.
0.0 to
255.0
*2
200.0 V
*2
No No No Yes Yes Yes 703H 4-13
Rated Voltage
T1-04
Motor rated
current
Set the rated current of the
motor in amps.
0.32 to
6.40
*4
1.90 A
*3
No Yes Yes Yes Yes Yes 704H 4-13
Rated Current
T1-05
Motor base
frequency
Set the base frequency of the
motor in hertz.
0.0 to
400.0
60.0 Hz No No No Yes Yes Yes 705H 4-13
Rated Fre-
quency
T1-06
Number of
motor poles
Set the number of motor
poles.
2 to 48
poles
4 poles No No No Yes Yes Yes 706H 4-13
Number of
Poles
T1-07
Motor base
speed
Set the base speed of the
motor in min
−1
.
0 to
24000
1750
min
−1
No No No Yes Yes Yes 707H 4-14
Rated Speed
T1-08
Number of
PG pulses
when turning
Set the number of pulses per
revolution for the PG being
used (pulse generator or
encoder) without any multi-
plication factor.
0 to
60000
600 No No Yes No Yes No 708H 4-14
PG Pulses/
Rev

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed CIMR-G7A and is the answer not in the manual?

YASKAWA Varispeed CIMR-G7A Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed CIMR-G7A
CategoryInverter
LanguageEnglish

Related product manuals