User Constant Tables
5-51
Analog Inputs: H3
User constants for analog inputs are shown in the following table.
31 During speed limit (ON: During speed limit) No No No Yes No 6-84
32
Speed control circuit operating for torque control (except when stopped).
The external torque reference will be limited if torque control is selected (internal
torque reference < external torque reference).
Output when the motor is rotating at the speed limit.
No No No Yes Yes
6-125
33 Zero-servo end (ON: Zero-servo function completed) No No No Yes No
6-84
6-141
37
During run 2 (ON: Frequency output, OFF: Base block, DC injection braking, ini-
tial excitation, operation stop)
Yes Yes Yes Yes Yes 6-83
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
H3-01
Signal level
selection (ter-
minal A1)
0: 0 to ±10V
1: 0 to ±10V
[11-bit + polarity (posi-
tive/negative) input]
0 or 1 0 No A A A A A 410H 6-26
Term A1 Sig-
nal
H3-02
Gain (termi-
nal A1)
Sets the frequency when 10 V
is input, as a percentage of the
maximum output frequency.
0.0 to
1000.0
100.0% Yes A A A A A 411H 6-26
Terminal A1
Gain
H3-03
Bias (termi-
nal A1)
Sets the frequency when 0 V
is input, as a percentage of the
maximum frequency.
-100.0
to
+100.0
0.0% Yes A A A A A 412H 6-26
Terminal A1
Bias
H3-04
Signal level
selection (ter-
minal A3)
0: 0 to ±10V
1: 0 to ±10V
[11-bit + polarity (posi-
tive/negative) input]
0 or 1 0 No A A A A A 413H
6-26
6-124
Term A3 Sig-
nal
H3-05
Multi-func-
tion analog
input (termi-
nal A3) func-
tion selection
Select from the functions
listed in the following table.
Refer to the next page.
0 to 1F 2 No A A A A A 414H
6-26
6-124
Terminal A3
Sel
H3-06
Gain (termi-
nal A3)
Sets the input gain (level)
when 10 V is input.
Set according to the 100%
value selected from H3-05.
0.0 to
1000.0
100.0% Yes A A A A A 415H
6-26
6-124
Terminal A3
Gain
H3-07
Bias (termi-
nal A3)
Sets the input gain (level)
when 0 V is input.
Set according to the 100%
value selected from H3-05.
-100.0
to
+100.0
0.0% Yes A A A A A 416H
6-26
6-124
Terminal A3
Bias
Set-
ting
Value
Function
Control Methods
Page
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2