User Constant Tables
5-73
o1-02
Monitor
selection after
power up
Sets the monitor item to be
displayed when the power is
turned on.
1: Frequency reference
2: Output frequency
3: Output current
4: The monitor item set for
o1-01
1 to 4 1 Yes A A A A A 501H 6-143
Power-On
Monitor
o1-03
Frequency
units of refer-
ence setting
and monitor
Sets the units that will be set
and displayed for the fre-
quency reference and fre-
quency monitor.
0: 0.01 Hz units
1: 0.01% units (Maximum
output frequency is
100%)
2 to 39:
min
−1
units (Sets the motor
poles.)
40 to 39999:
User desired display
Set the desired values for
setting and display for the
max. output frequency.
Example: When the max. out-
put frequency value is 200.0,
set 12000
0 to
39999
0 No A A A A A 502H
6-143
6-161
Display Scal-
ing
o1-04
Setting unit
for frequency
constants
related to V/f
characteris-
tics
Set the setting unit for fre-
quency reference-related con-
stants.
0: Hz
1: min
−1
0 or 1 0 No No No No A A 503H 6-143
V/f Display
Unit
o1-05
LCD bright-
ness adjust-
ment
Set a smaller value to lighten
the LCD and a larger value
to darken the LCD (stan-
dard: 3).
0 to 5 3 Yes No No No A A 504H -
LCD Contrast
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Page
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
Set 4-digit number
excluding the decimal
point.
Set the number of digits
below the decimal point
to display.