6-52
Multi-function Output (H2-01 to H2-05)
L6-04
Torque detec-
tion selection
2
Multi-function output for
overtorque detection 1 is output to
multi-function contact output when
overtorque detection 1 NO or
overtorque detection 1 NC is
selected. Multi-function output for
overtorque detection 2 is output to
multi-function contact output when
overtorque detection 2 NO or
overtorque detection 2 NC is
selected.
0 to 8 0 NoAAAAA
Torq Det 2
Sel
L6-05
Torque detec-
tion level 2
0 to
300
150% No A A A A A
Torq Det 2
Lvl
L6-06
Torque detec-
tion time 2
0.0 to
10.0
0.1 s No A A A A A
Torq Det 2
Time
Set-
ting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
1
Flux
Vec-
tor
Open
Loop
Vec-
tor
2
B
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque detec-
tion at ON)
Yes Yes Yes Yes Yes
17
Overtorque/undertorque detection 1 NC (NC Contact: Overtorque/undertorque detec-
tion at OFF)
Yes Yes Yes Yes Yes
18
Overtorque/undertorque detection 2 NO (NO Contact: Overtorque/undertorque detec-
tion at ON)
Yes Yes Yes Yes Yes
19
Overtorque/undertorque detection 2 NC (NC Contact: Overtorque/undertorque detec-
tion at OFF)
Yes Yes Yes Yes Yes
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2