7-14
BUS
(blinking)
Option
Com Err
Option Board Communications
Error
A communications error occurred in a
mode where the Run Command or a
frequency reference is set from an
Communications Option Board.
-
Check the communications devices
and signals.
CALL
(blinking)
Com
Call
Communications on Standby
Control data was not normally
received when power was turned ON.
-
Check the communications devices
and signals.
E-15
(blinking)
SI-F/G
Com Err
SI-F/G Communications Error
Detected
A communications error was detected
when a Run Command or frequency
reference was set from an option
board and continuous operation was
set for the E-15 operation selection.
- Check the communications signals.
RUNC
(blinking)
Ext Run
Active
Reset during Run Command Input
Error
The reset signal was input during Run
Command input from an external ter-
minal or other source.
-
Check that a Run Command is not
being input from an external terminal
or other source.
Table 7.2 Alarm Displays and Processing (Continued)
Display Meaning Probable causes Corrective Actions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Varispeed CIMR-G7A and is the answer not in the manual?

YASKAWA Varispeed CIMR-G7A Specifications

General IconGeneral
BrandYASKAWA
ModelVarispeed CIMR-G7A
CategoryInverter
LanguageEnglish

Related product manuals