7-16
OPE11
Carr Freq/
On-Delay
Constant Setting Error
One of the following constant setting errors exists.
• C6-05 (Carrier Frequency Gain) > 6, the Carrier Frequency Lower Limit (C6-04)
> the Carrier Frequency Gain (C6-05)
• Upper/lower limit error in C6-03 to 05.
• C6-01 is 0 and C6-02 is 2 to E.
• C6-01 is 1 and C6-02 is 7 to E.
ERR
EEPROM
R/W Err
EEPROM Write Error
A verification error occurred when writing EEPROM.
• Try turning the power supply off and on again.
• Try setting the constants again.
Table 7.3 Operation Error Displays and Incorrect Settings (Continued)
Display Meaning Incorrect settings