EasyManua.ls Logo

YASKAWA Z1000 - Preface & General Safety

YASKAWA Z1000
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Replace Table 3.3 pages 79 and 80
nn
Three-Phase 400 V Class
Table 3.3 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
Model CIMR-Zoo
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
4A0005
4A0008
4A0011
R/L1, S/L2, T/L3 14
14 to 8
M4
1.6 to 1.8
(14 to 16)
U/T1, V/T2, W/T3 14
-M, +M
M5
2.7 to 3.0
(24 to 27)
4A0014
R/L1, S/L2, T/L3 12
14 to 8
M4
1.6 to 1.8
(14 to 16)
U/T1, V/T2, W/T3 12
-M, +M
M5
2.7 to 3.0
(24 to 27)
4A0021
R/L1, S/L2, T/L3 10
14 to 8
M4
1.6 to 1.8
(14 to 16)
U/T1, V/T2, W/T3 10
-M, +M
M5
2.7 to 3.0
(24 to 27)
4A0027
R/L1, S/L2, T/L3 8
14 to 8
M4
1.6 to 1.8
(14 to 16)
U/T1, V/T2, W/T3 8
-M, +M
M5
2.7 to 3.0
(24 to 27)
4A0034
<1>
R/L1, S/L2, T/L3 8
10 to 4 M5
2.7 to 3.0
(24 to 27)
U/T1, V/T2, W/T3 8
-M, +M
4A0040
<1>
R/L1, S/L2, T/L3 8
10 to 4 M5
2.7 to 3.0
(24 to 27)
U/T1, V/T2, W/T3 8
-M, +M
4A0052
<1>
R/L1, S/L2, T/L3 6
8 to 2/0 M8
5.4 to 6.0
(48 to 53)
U/T1, V/T2, W/T3 6
-M, +M
4A0065
<1>
R/L1, S/L2, T/L3 4
8 to 2/0 M8
5.4 to 6.0
(48 to 53)
U/T1, V/T2, W/T3 4
-M, +M
4A0077
<1>
R/L1, S/L2, T/L3 3
8 to 2/0 M8
5.4 to 6.0
(48 to 53)
U/T1, V/T2, W/T3 3
-M, +M
4A0096
<1>
R/L1, S/L2, T/L3 1
8 to 2/0 M8
5.4 to 6.0
(48 to 53)
U/T1, V/T2, W/T3 1
-M, +M
4A0124
<1>
R/L1, S/L2, T/L3 2/0
8 to 2/0 M8
5.4 to 6.0
(48 to 53)
U/T1, V/T2, W/T3 2/0
-M, +M
3.8 Main Circuit Wiring
YASKAWA ELECTRIC TOEP C710616 45B YASKAWA AC Drive – Z1000 User Manual
81
3
Electrical Installation
6 Replace Table 3.3 pages 79 and 80
YASKAWA TOEP YAISUP 04A YASKAWA AC Drive – Z1000 User Manual Supplement
11

Other manuals for YASKAWA Z1000

Related product manuals