NOTE
• For excitation cables, always use a crimp terminal
with an insulation cover.
• Use crimp tools from the manufacturer of the crimp
terminal you want to use to connect the crimp
terminal and cable.
• Use crimp tools that are appropriate for the
diameter of the cable to be connected.
4.2.3 Wiring Ports for Remote Flowmeter
This instrument is of watertight construction as stipulated
inJISC0920.Itisshippedwithawiringbracket
(waterproof gland or waterproof gland with union) or a
plastic gland attached, only in cases where an optional
specicationisselectedforthewiringport.Incaseofthe
explosion proof type, refer to chapter 10.
IMPORTANT
The wiring port is sealed with a cap (not waterproof).
Do not remove the cap from the unused wiring port.
If waterproof property is necessary, apply a blanking
plug to the unused wiring port.
The blanking plug may not be attached depending on
thespecication.
If it is necessary, contact YOKOGAWA.
(1) When waterproof property is unnecessary
(When there are no particular optional
specications)
The wiring port is sealed with a cap (not water-proof) that
must be removed before wiring. At this time, handle the
wiringportinaccordancewiththeJISC0920mentioned
above. Do not remove the cap from the unused wiring
port.
(2) When waterproof property is necessary
(Wiring using waterproof glands)
IMPORTANT
To prevent water or condensation from entering the
converter housing, waterproof glands are recommended.
Do not over-tighten the glands or damage to the cables
may result. Tightness of the gland can be checked by
conrmingthatthecableisheldrmlyinplace.
Forworkingontheelectricwiretubesortheexibletubes
(G1/2), remove the waterproof gland and attach them
directly to the wiring port.
Gasket
Figure 4.2.6 Plastic Gland (Optional code EP)
(3) Conduit Wiring
When wiring the conduits, pass the conduit through the
wiring connection port, and utilize the waterproof gland to
preventwaterfromowingin.Placetheconduitpipeon
an angle as shown in Figure 4.2.7
Install a drain valve at the low end of the vertical pipe, and
open the valve regularly.