F0460.ai
Mechanical Counter
Electronic Counter
Load
Protective diode
30V DC, 0.2A. max
PULSE OUT
PULSE OUT
AXFA11
AXFA11
P+
P-
P+
P-
Figure 4.4.13  Pulse Output Connection
F0461.ai
Protective diode
PULSE OUT
AXFA11
AXFA11
P+
P-
P+
P-
Output voltage: 24 V DC ±20%
 
 
Current: 150 mA or less
 
 
Pulse rate: 0.0001 to 2 pps
 
 
Pulse width: 20, 33, 50, 100 ms
Mechanical Counter
Electronic Counter
Load
PULSE OUT
Figure 4.4.14   Active Pulse Output Connection  
(Optional code EM)
  Status Input
IMPORTANT
Status inputs are designed for use with no-voltage 
(dry) contacts. Be careful not to connect the status to 
any signal source carrying voltage.
Applying voltage may damage the input circuit.
AXFA11
SI1
+
SI2
+
COM
F0462.ai
No-voltage status input
Closed: Less than 200 Ω
Open:  More than 100 kΩ
Figure 4.4.15  Status Input Connection
  Status Output / Alarm Output
IMPORTANT
Since this is an isolated transistor output, be careful of 
voltage and polarity when wiring.
Do not apply a voltage larger than 30V DC or a current 
larger than 0.2A in order to prevent damage to the 
instrument.
This output cannot switch an AC load. To switch an AC 
load, an intermediate relay must be inserted as shown 
in Figure 4.4.16 or Figure 4.4.17.
* The alarm output operates from closed (normal) to open 
(alarm occurrence) by factory default setting. Changes 
can be made via the parameter settings.
F0463.ai
Load
Load
Protective diode
Protective 
diode
External power supply
 30V DC, 0.2A. max
AXFA11
External power supply
 30V DC, 0.2A. max
AXFA11
This connection is not possible.
This connection is not possible.
SO1
+
SO2
+
COM
SO1
+
SO2
+
COM
Electromagnetic 
valve
Electromagnetic 
valve
AC power supply
Relay
Figure 4.4.16  Status Output Connection
F0464.ai
Load
Protective diode
External power supply
 30V DC, 0.2A. max
AXFA11
AXFA11
This connection is not possible.
AL
+
AL
-
AL
+
AL
-
Electromagnetic 
valve
AC power supply
Relay
Figure 4.4.17  Alarm Output Connection