<10. EXPLOSION PROTECTED TYPE INSTRUMENT>
10-12
IM 01F06F00-01EN
(2) Wiring
•Explosionproof
WARNING
All wiring shall comply with Canadian
Electrical Code Part I and Local Electrical
Codes.
In Hazardous locations, wiring shall be in
conduit as shown in the gure.
A SEAL SHALL BE INSTALLED WITHIN
50cm OF THE ENCLOSURE.
When the equipment is installed in Division
2, “FACTORY SEALED, CONDUIT SEAL
NOT REQUIRED”.
(3) Operation
•Explosionproof
WARNING
Note a warning label worded as follows.
Warning: OPEN CIRCUIT BEFORE
REMOVING COVER.
Take care not to generate mechanical
spark when access to the instrument and
peripheral devices in hazardous locations.
(4) Maintenance and Repair
WARNING
The instrument modication or part replacements
by other than authorized representatives of
Yokogawa Electric Corporation are prohibited
and will void CSA Certication.
(5) Dual Seal (Option /CF11)
Dual Seal:
Certied by CSA to the requirement of ANSI/ISA
12.27.01
No additional sealing required.
Primary seal failure annunciation: at the O-ring
seal portion between shedder bar and amplier
housing.