<Toc> <2. Initial Settings>
2-5
IM 05D01D02-41E
Instrument Input Range Codes
Input Type
Instrument Input
Range Code
Instrument
Input Range
Measurement Accuracy
OFF
1
-200 to 1370C
Set the data item PV Input Type "IN" to the OFF option to leave the PV input
type undefined.
2
K
J
4
5
T
6
0.1% of instrument range 1 digit for temperatures
equal to or higher than 0
C
0.2% of instrument range 1 digit for temperatures
below 0
C
0.1% of instrument range 1 digit for temperatures
equal to or higher than 0
C
0.2% of instrument range 1 digit for temperatures
below 0
C
B7
0.15% of instrument range 1 digit at 400
C or more
5% of instrument range 1 digit at less than 400
C
S
8
R
9
0.15% of instrument range 1 digit
N
10
0.1% of instrument range 1 digit
0.25% of instrument range 1 digit for temperatures
below 0
C
E
11
L(DIN)
12
13
U(DIN)
14
W
15
0.2% of instrument range 1 digit
Platinel 2
16
0.1% of instrument range 1 digit
PR20-40 17
0.5% of instrument range 1 digit at 800
C or more
No accuracy is guaranteed at less than 800
C
Thermocouple
Unspecified
W97Re3-
W75Re25
18
0.2% of instrument range 1 digit
30
0.1% of instrument range 1 digit (Note 1) (Note 2)
JPt100
31
0.2% of instrument range 1 digit (Note 1)
35
36
0.1% of instrument range 1 digit (Note 1) (Note 2)
RTD
Pt100
37
0.2% of instrument range 1 digit (Note 1)
0.4 to 2 V
40
Standard
signal
1 to 5 V 41
0 to 2 V 50
0 to 10 V 51
0.400 to 2.000 V
1.000 to 5.000 V
0.000 to 2.000 V
0.00 to 10.00 V
-10 to 20 mV
55 -10.00 to 20.00 mV
DC voltage
0 to 100 mV
56 0.0 to 100.0 mV
0.1% of instrument range 1 digit
The read-out range can be scaled between -1999 to
9999.
3
-300 to 2500F
-199.9 to 999.9C
0 to 2300F
-199.9 to 500.0C
-199.9 to 999.9F
-199.9 to 999.9C
-300 to 2300F
-199.9 to 400.0C
-300 to 750F
0.0 to 400.0C
-199.9 to 750.0F
0 to 1800C
32 to 3300F
0 to 1700C
32 to 3100F
0 to 1700C
32 to 3100F
-200 to 1300C
-300 to 2400F
-199.9 to 999.9C
-300 to 1800F
-199.9 to 900.0C
-300 to 1300F
-199.9 to 400.0C
-300 to 750F
0.0 to 400.0C
-199.9 to 750.0F
0 to 2300C
32 to 4200F
0 to 1390C
32 to 2500F
0 to 1900C
32 to 3400F
0 to 2000C
32 to 3600F
-199.9 to 500.0C
-199.9 to 999.9F
-150.0 to 150.0C
-199.9 to 300.0F
-199.9 to 850.0C
-300 to 1180F
-199.9 to 500.0C
-199.9 to 999.9F
-150.0 to 150.0C
-199.9 to 300.0F
* Performance in the standard operating condition (at 232C, 5510%RH, and 50/60Hz power frequency)
Note 1: The accuracy is 0.3C of instrument range 1 digit for a temperature range from 0C to 100C.
Note 2: The accuracy is 0.5C of instrument range 1 digit for a temperature range from -100C to 200C.
* To receive a 4-20 mA DC signal, select a standard signal of 1 to 5 V DC and connect it to a 250 resistor. This resistor
is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
NOTE
The controller may automatically initialize the registered operating parameter setpoints if
any change is made to the data item PV Input Type (IN), Maximum Value of PV Input
Range (RH), Minimum Value of PV Input Range (RL), PV Input Decimal Point Position
(SDP), Maximum Value of PV Input Scale (SH) or Minimum Value of PV Input Scale (SL).
After a change has been made to any of these data items, be sure to verify the registered
operating parameter setpoints to ensure that they are correct. If any data item has been
changed to its default, set it to a required value.
1st Edition : May 31,2000-00

Other manuals for YOKOGAWA UT320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA UT320 and is the answer not in the manual?

YOKOGAWA UT320 Specifications

General IconGeneral
BrandYOKOGAWA
ModelUT320
CategoryController
LanguageEnglish