505428-YTG-V-0417
Johnson Controls Unitary Products 67
NC090 C00C (CONSTANT VOLUME)
2.0
208-3-60 6.6
None --- --- --- 8.3 15
10 KW 7.5 1 20.8 34.3 35
16 KW 12 2 33.4 49.9 50
26 KW 19.5 2 54.2 75.9 80
36 KW 27 2 75.1 101.9 110
230-3-60 6.8
None --- --- --- 8.5 15
10 KW 10 1 24.1 38.6 40
16 KW 16 2 38.5 56.6 60
26 KW 26 2 62.5 86.7 90
36 KW 36 2 86.6 116.8 125
460-3-60 3.4
None --- --- --- 4.3 15
10 KW 10 1 12 19.3 20
16 KW 16 2 19.2 28.3 30
26 KW 26 2 31.3 43.3 45
36 KW 36 2 43.3 58.4 60
575-3-60 2.4
None --- --- --- 3 15
10 KW 10 1 9.6 15 15
16 KW 16 2 15.4 22.2 25
26 KW 26 2 25 34.3 35
36 KW 36 2 34.6 46.3 50
NL090 (NL/NM) 120 C00C (INTELLISPEED)
2.0
208-3-60 5.8
None --- --- --- 7.3 15
10 KW 7.5 1 20.8 33.3 35
16 KW 12 2 33.4 48.9 50
26 KW 19.5 2 54.2 74.9 80
36 KW 27 2 75.1 100.9 110
230-3-60 5.8
None --- --- --- 7.3 15
10 KW 10 1 24.1 37.3 40
16 KW 16 2 38.5 55.4 60
26 KW 26 2 62.5 85.4 90
36 KW 36 2 86.6 115.5 125
460-3-60 2.9
None --- --- --- 3.6 15
10 KW 10 1 12.0 18.7 20
16 KW 16 2 19.2 27.7 30
26 KW 26 2 31.3 42.7 45
36 KW 36 2 43.3 57.8 60
575-3-60 2.2
None --- --- --- 2.8 15
10 KW 10 1 9.6 14.8 15
16 KW 16 2 15.4 22 25
26 KW 26 2 25.0 34 35
36 KW 36 2 34.6 46.1 50
Electrical Data - Evaporator Units (Continued)
Motor HP Power Supply
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
FLA Model KW Stages Amps

Table of Contents