505428-YTG-V-0417
68 Johnson Controls Unitary Products
(NC/ND)120 C00D (CONSTANT VOLUME)
2.0
208-3-60 6.0
None --- --- --- 7.5 15
10 KW 7.5 1 20.8 33.5 35
16 KW 12 2 33.4 49.1 50
26 KW 19.5 2 54.2 75.2 80
36 KW 27 2 75.1 101.2 110
230-3-60 5.8
None --- --- --- 7.3 15
10 KW 10 1 24.1 37.3 40
16 KW 16 2 38.5 55.4 60
26 KW 26 2 62.5 85.4 90
36 KW 36 2 86.6 155.5 125
460-3-60 2.9
None --- --- --- 3.6 15
10 KW 10 1 12 18.7 20
16 KW 16 2 19.2 27.7 30
26 KW 26 2 31.3 42.7 45
36 KW 36 2 43.3 57.8 60
575-3-60 2.2
None --- --- --- 2.8 15
10 KW 10 1 9.6 14.8 15
16 KW 16 2 15.4 22 25
26 KW2622534 35
36 KW 36 2 34.6 46.1 50
(NC/ND)120 C00D (CONSTANT VOLUME)
3.0
208-3-60 8.3
None --- --- --- 10.4 15
10 KW 7.5 1 20.8 36.4 40
16 KW 12 2 33.4 52.0 60
26 KW 19.5 2 54.2 78.0 80
36 KW 27 2 75.1 104.2 110
230-3-60 8.2
None --- --- --- 10.3 15
10 KW 10 1 24.1 40.3 45
16 KW 16 2 38.5 58.4 60
26 KW 26 2 62.5 88.4 90
36 KW 36 2 86.6 118.5 125
460-3-60 4.1
None --- --- --- 5.1 15
10 KW 10 1 12 20.2 25
16 KW 16 2 19.2 29.2 30
26 KW 26 2 31.3 44.2 45
36 KW 36 2 43.3 59.3 60
575-3-60 3.1
None --- --- --- 3.9 15
10 KW 10 1 9.6 15.9 20
16 KW 16 2 15.4 23.1 25
26 KW 26 2 25 35.1 40
36 KW 36 2 34.6 47.2 50
Electrical Data - Evaporator Units (Continued)
Motor HP Power Supply
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
FLA Model KW Stages Amps

Table of Contents