8. Main Menu: Schedule:
Setup a Schedule and Holidays
Constant Volume Heat Pump Configuration
1. Main Menu: Advanced: Application:
App = Heat Pump
Opt = # Compressor Stages / with or
without Emergency Heat
2. Main Menu: Advanced: Application:
Additional Setup: Sensors:
OAT Sensor = Yes
SAT Sensor = Yes
3. Main Menu: Advanced: Application:
Additional Setup: Valve:
Check Reversing Valve Active Mode
4. Main Menu: Advanced: Application:
Additional Setup: Fan:
Speeds: Constant
Unocc: On or Auto
Occ: On or Auto
5. Main Menu: Advanced: Application:
SAT Control = None