Glossary
BAUD RATE: Default is 38400 and options available include 9600, 19200, 38400 and 76800.
CO2 SETPT (PPM): Space CO
2
override setpoint. Default setpoint is 1100 ppm and range is
500-1800 ppm.
COMP1 MIN OFF (SECS): Compressor minimum off time. Default is 120 seconds and range
is 120-600 seconds.
COMP1 MIN ON (SECS): Compressor minimum on time. Default is 120 seconds and range is
0-600 seconds.
COMP OAT LOW: Compressor cooling outside air temperature lockout. Default is 40°F and
range is 0-50°F.
COMP STG DELAY (MINS): Compressor stage delay. Used for cooling and heat pump
heating. Default is 3 minutes and range 2-15 minutes.
COOL SETBACK: Unoccupied cooling space temperature setpoint. Default setpoint is 80°F.
COOL SETPT : Occupied cooling space temperature setpoint. Default setpoint is 74°F and
range is 55-90°F.
DAMPER - CNTRL (0-100%): Available options are 0-10 VDC, 10-0 VDC, 2-10 VDC or 10-
2 VDC. Default value is 2-10 VDC.
DAMPER - ECON: Available economizer options are None or Modulating.
DAMPER - ECON ENBLE TEMP: Economizer enable outside air temperature setpoint.
Default setpoint is 60°F and range is 50-70°F.
DAMPER - ENTHALPY: Available economizer options are Enable or Disable.
DAMPER - LOW LIMIT ALARM: Economizer supply air temperature low limit which
returns the economizer to the minimum position. Default value is 45°F and range is 0-100°F.
DAMPER - MIN POSITION (%): Minimum economizer damper position. Default value is
10% and range is 0-95%.
DEADBAND: Space temperature setpoint deadband. Default setpoint deadband is 2°F and range
is 2-15°F.
DEHUM DEADBAND: Space humidity setpoint deadband. Default setpoint is 5% RH and
range is 5-15% RH.
DEHUM PRIORITY: Available dehumidification priority options are True or False.
DEHUM SETPT: Occupied space relative humidity setpoint. Default setpoint is 50% RH and
range is 20-85% RH.