FAN - COOL MAX SPEED: Maximum cooling speed of a variable speed fan. Default is
100%, range is 50-100% and value must be greater than the minimum cooling speed.
FAN - COOL MIN SPEED: Minimum cooling speed of a variable speed fan. Default is 30%,
range is 30-80% and value must be less than the maximum cooling speed.
FAN - DEHUM SPEED: Dehumidification speed of a variable speed fan. Default is 50% and
range is 25-75%
FAN - HEAT MAX SPEED: Maximum heating speed of a variable speed fan. Default is 100%,
range is 50-100% and value must be greater than the minimum heating speed.
FAN - HEAT MIN SPEED: Minimum heating speed of a variable speed fan. Default is 50%
for non-heat pump units, 75% for heat pump units, range is 50-100% and value must be less than
the maximum heating speed.
FAN - OFF DELAY (SECS): Amount of time the fan will continue to run after heating and
cooling is deactivated with Auto fan operation. Default value is 180 seconds and range is 0-600
seconds.
HEAT - DELAY (MINS): Stage delay between auxiliary heating stages. Default value is 3
minutes and range is 3-60 minutes.
HEAT1 MIN OFF (SECS): Heating minimum off time. Default is 120 seconds and range is
120-600 seconds.
HEAT1 MIN ON (SECS): Heating minimum on time. Default is 120 seconds and range is 120-
600 seconds.
HEAT SETBACK: Unoccupied heating space temperature setpoint. Default setpoint is 64°F.
HEAT SETPT: Occupied heating space temperature setpoint. Default setpoint is 70° F and
range is 55-90°F.
HTG OAT HIGH: Auxiliary heating outside air temperature lockout. Heat pump heating will
still be available. Default is 70°F and range is 50-150°F.
INACTIVITY (SECS): Amount of time the backlight will stay on and the current password will
stay active after the last button push. Default value is 60 seconds and range is 5-600 seconds.
MAC ADDRESS: Default is 1 and range is 0-127. Best practice is to assign the MAC
ADDRESS in sequence for most efficient communication.
MAX DGTL COMP: Maximum allowable capacity of the variable capacity scroll compressor.
Default is 100% and range is 25-100% and value must be 5% greater than the minimum variable
capacity scroll compressor capacity setpoint.
MAX MASTER: Default is 127 and range is 0-127. Best practice is to set the MAX MASTER
to the highest assigned MAC ADDRESS.
MIN DGTL COMP: Minimum allowable capacity of the variable capacity scroll compressor.
Default is 50%, range is 20-80% and value must be 5% less than the maximum variable capacity
scroll compressor capacity setpoint.