46
MIN SETPT DIFF: Minimum setpoint differential between the cooling and heating space
temperature setpoints. Used for both the occupied and unoccupied modes of operation. Default
setpoint differential is 2°F and range is 1-15°F.
OAT HIGH: Description. Default is 150°F and range is 110-160°F.
OAT LOW: Description. Default is -40°F and range is -50-40°F.
OCC MAX CLG: Occupied maximum cooling space temperature setpoint. Default is 78°F and
range is 55-92°F.
OCC MIN CLG: Occupied minimum cooling space temperature setpoint. Default is 68°F and
range is 55-90°F.
OCC MAX HTG: Occupied maximum heating space temperature setpoint. Default is 72°F and
range is 55-90°F.
OCC MIN HTG: Occupied minimum heating space temperature setpoint. Default is 65°F and
range is 53-90°F.
OCC OVRIDE (HRS): Amount of time a space temperature setpoint override and occupancy
override will last. Default value is 1 hour and range is 0-12 hours. When set at 0, the override
will last until the next schedule change.
SAT COOL SETPT: Cooling supply air temperature setpoint. Default setpoint is 55°F and
range is 50-70°F.
SAT HEAT SETPT: Heating supply air temperature setpoint. Default setpoint is 120°F and
range is 75-200°F.
SAT HIGH: Maximum supply air temperature. Default is 200°F and range is 120-250°F.
Disable all outputs.
SAT LOW: Minimum supply air temperature. Default is 40°F and range is 32-60°F. Disable all
outputs.
SUCTION (PSI): Dehumidification suction pressure setpoint. Default setpoint is 119.4 psi and
range is 50-250 psi.
UNOCC DEHUM SETPT: Unoccupied space humidity setpoint. Default setpoint is 65% RH
and range is 20-85% RH.
UNOCC MAX HTG: Unoccupied maximum heating space temperature setpoint. Default is
72°F and range is 55-90°F.
UNOCC MIN CLG: Unoccupied minimum cooling space temperature setpoint. Default is 68°F
and range is 55-90°F.