EasyManua.ls Logo

AAON SS1079 - Initial Setup and Module Configuration

AAON SS1079
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VCC-X Operator Interface SD
VCC-X CONFIGURATION
25
Confi guration Screens
In order to correctly set up the VCC-X Controller, you must fi rst
confi gure several parameters in regard to the type of HVAC unit
and system you have installed. Most of these values and operat-
ing parameters are only set once at the initial system setup and are
never changed.
Modular Service Tool Instructions
No matter what screen or menu you’re in, press <CONFIGURA-
TION>. The Unit Selection Screen will appear, shown below, request-
ing that you enter the unit ID number.
VCC-X CONFIGURATION
RSM CONFIGURATION
Select & Press Enter
Enter the Unit ID of the controller you wish to search and press
<ENTER>. Once communication is established, “No Communica-
tion” will be replaced with “Press Down.” Then press <>. Select
VCC-X Confi guration and then press
<ENTER>. Press <ENTER>
to save entered data and press <> to scroll through the screens.
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
System Manager SD Instructions
From any Main screen, press <SETPOINTS>. The screen below
will appear because this option requires passcode clearance. Only a
Level 2 passcode can change setpoints.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
If the correct passcode was entered, the Unit Selection Screen will
be displayed.
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication
Enter the Unit ID of the controller you wish to search and press
<ENTER>. Once communication is established, “No Communica-
tion” will be replaced with “Press Down.” Then press <>.
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
The following screen will be displayed:
Change Setpoints
Configure Unit
Save/Copy/Restore
VCC-X CONFIGURATION
RSM CONFIGURATION
Select & Press Enter
On the fi rst screen, scroll down to the ‘Confi gure Unit’ option and
press <ENTER>. On the second screen, select VCC-X Confi guration
and then press <ENTER>. This will take you to the fi rst Confi gura-
tion Screen shown below.
Confi guration Screen #1 - Sensor Scaling
VCC-X Cnfg ID #
Sensor Scaling
Fahrenheit
USE < or > TO CHANGE
Options are Fahrenheit or Celsius. If you make a change to this
screen, after you press <ENTER> to have the system accept the
change, you must return to the Unit Selection Screen to re-establish
communications with the Controller. Default is Fahrenheit.
Confi guration Screen #2 - RSM #1 & #2
Module Installed
VCC-X Cnfg ID #
RSM#1 Installed: NO
RSM#2 Installed: NO
USE < or > TO CHANGE
If you have a one RSM Module installed, the 1st confi guration op-
tion should be confi gured as YES. If you have a 2nd RSM Module
installed, the 2nd confi guration option should be confi gured as YES.
Default is NO.
VCC-X Confi guration Screens
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication