EasyManua.ls Logo

AAON SS1079 - VAV;ZONE DAMPER FORCE; VAV;Zone Damper Force Modes

AAON SS1079
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VAV/ZONE DAMPER FORCE
81
VCC-X Operator Interface SD
VAV/Zone Damper Force Modes
Damper Force Modes
Damper Force Modes are available for testing or balancing the sys-
tem. These Force Modes can be accessed and programmed from
the Modular Service Tool.
Modular Service Tool Instructions
When using the Modular Service Tool, simply press the <BALANCE
- TEST>
key. You will then see the Unit ID Screen. Enter the unit
ID of the controller you wish to access and
press <ENTER>. Once
communication is established, “No Communication” will be replaced
with “Press Down.” Then
press <>.
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
The following screen will be displayed:
Damper Force
Para Blocks
Load / Save / Copy
With the cursor on Damper Force, press <ENTER> to access the
Damper Force Mode Screen.
Dampers Force Mode Screen
If the unit ID you entered is for a VCC-X Controller that has VAV/
Zone Controllers connected to its communication loop, the Damper
Force Mode will act as a “Global” Damper Force Mode. That is, all
VAV/Zone Controllers on that VCC-X Controller’s communication
loop will be forced to the same Damper Force Mode setting. If the
unit ID you entered is for a VAV/Zone Controller, the Damper Force
Mode setting will only apply to that VAV/Zone Controller.
Damper Force
Enter Force Mode: 0
0=Auto 1=Open 2=Clsd
3=Max 4=Min 5=Fixed
Set the appropriate Damper Force Mode by entering numbers 0
through 5. Following is a list of the force modes and their meaning:
0 = Auto This is the default setpoint. With this setting,
the damper will operate normally and modulate
according to the controller setpoints.
1 = Open This setting will force the dampers to their
fully-open position.
2 = Clsd This setting will force the damper to its fully-
closed position.
3 = Max This setting will force the damper to its
Maximum Position Setpoint. See VAV/Zone
Controller Setpoint Screen #5 on page 76 for
complete setpoint information.
4 = Min This setting will force the damper to its
Minimum Position Setpoint. See
VAV/Zone
Controller Setpoint Screen #5
on page 76 for
complete setpoint information.
5 = Fixed This setting will force the damper to a xed
position based on the Fixed Position Setpoint.
See
VAV/Zone Controller Setpoint Screen #8
on page 77 for complete setpoint information.
CAUTION: The Damper Force Modes should only be used
by quali ed service personnel. Serious dam-
age to the ductwork could result if the dampers
are all forced closed and the HVAC unit fan
is operating.

Related product manuals