APPENDIX A - SAVE, LOAD, COPY SETPOINTS
86
VCC-X Operator Interface SD
Modular Service Tool Instructions
From any menu screen, press <BALANCE-TEST>. The Unit Selec-
tion Screen
will appear requesting that you enter the unit ID number.
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication
Enter the network unit ID for the controller you want to save the
setpoints from. Example, ‘102’ for Loop 1 / Unit 2. Then press
<ENTER>. Once communication is established, “No Communica-
tion” will be replaced with “Press Down.” After a brief pause, press
<> to get to the Balance - Test Screen shown below.
Outputs Force
Para Blocks
Save/Copy/Restore
Scroll down to the ‘Save/Copy/Restore’ option and press <ENTER>.
This will take you to the Save Setpoints screen.
System Manager SD Instructions
From any Main screen, press <SETPOINTS>. The screen below
will appear because this option requires passcode clearance. Only a
Level 2 passcode can change setpoints.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
If the correct passcode was entered, the Unit Selection Screen will
be displayed.
Enter Unit Address
Then Press Enter
Selected Unit#: XXXX
No Communication
Enter the Unit ID of the controller you wish to save the setpoints from
and press <ENTER>. Once communication is established, “No Com-
munication” will be replaced with “Press Down.” Then
press <>.
NOTE: If “No Communication” remains, it indicates a
communication failure to the controller.
The following screen will be displayed:
Change Setpoints
Configure Unit
Save/Copy/Restore
Scroll down to the ‘Save/Copy/Restore’ option and press <ENTER>.
This will take you to the Save Setpoints screen.
Save Setpoints - Network Mode
From the Save Setpoints Screen shown below:
Save Setpoints
Press Enter To Save
Press <ENTER> and a setpoint fi le will be saved to the SD card.
You will receive a message that the save was successful. This fi le
is specifi c to this controller on this loop.