EasyManuals Logo

AAON SS1079 User Manual

AAON SS1079
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #83 background imageLoading...
Page #83 background image
VCC-X Operator Interface SD
MINILINK PD CONFIGURATION
83
MiniLink PD Con guration and Status Screens
Con guration Screen #4 - Optimal Start
Target Zone
Polling Unit Config
Optimal Start
Target Zone..: XXX
[Enter Target Zone]
This is the unit ID of the Zone that you want to be satis ed by the
normally scheduled start time. If you enter “-1” into this box, it will
average all zones instead of picking a speci c zone. If you do not
require Optimal Start, enter “0”.
Con guration Screen #5 - Maverick Testing
Polling Unit Config
Maverick Testing
Disabled: YES
Use < Or > To Change
Disabling the Maverick Testing allows known troubled zone(s) to
continue voting without causing a Maverick alarm. In other words,
all zones are included in the voting regardless of whether they are
more than four degrees from setpoint.
Con guration Screens #6-65 - Alarm Polling
Polling Unit Config
Enable Alarm Polling
Unit XX : YES
Use < Or > To Change
Enabling Alarm Polling allows any alarm from the loop to be polled.
You must set this for each controller on the loop.
MiniLink PD Status
Status Screen #1 - Schedule Mode, System
Status, and Minutes Left
Polling Device
System Occupied
Venting Mode
XXX Min Left in Mode
Line 2 Current Schedule Mode
Can be System Occupied or System Unoccupied.
Line 3 Currently System Status
Can be Vent Mode, Cooling Mode, or Heat Mode.
Line 4 Minutes Left In Mode
The number of minutes left in the current mode of
operation before it can switch modes. This value is
user-adjustable. See Con guration Screen #3.
Status Screen #2 - Mode Priority, Cool Total,
and Heat Total
Polling Device
No Mode Priority
Cool Total.: XX.XºF
Heat Total.: XX.XºF
Line 2 Mode Priority
Can be Heat Priority or Cool Priority. This is based
on the voting zones and their demand.
Line 3 Cool Total
Total cooling temperature demand from all zones.
Line 4 Heat Total
Total heating temperature demand from all zones.