VCC-X CONFIGURATION
VCC-X Operator Interface SD
36
Confi guration Screen #64 - Broadcast OA RH
VCC-X Cnfg ID #
Broadcast OA RH
NO
USE < or > TO CHANGE
The VCC-X can broadcast its Outdoor Air Humidity Reading to
other HVAC units if they are not equipped with their own Outdoor
Air RH sensors. A network communications device (MiniLink PD
or CommLink) is needed in order for this feature to operate. Select
YES for Broadcast Outdoor RH. Default is NO.
Confi guration Screen #65 - Broadcast Space
Temperature
VCC-X Cnfg ID #
Broadcast SPC Temp
NO
USE < or > TO CHANGE
The VCC-X can broadcast its Space Temperature Reading to other
HVAC units if they are not equipped with their own Space Tem-
perature sensors. A network communications device (MiniLink PD
or CommLink) is needed in order for this feature to operate.
Select
YES for Broadcast Space Temperature. Default is NO.
Confi guration Screen #66 - Broadcast Space
Humidity
VCC-X Cnfg ID #
Broadcast SPC RH
NO
USE < or > TO CHANGE
The VCC-X can broadcast its Space Humidity Reading to other
HVAC units if they are not equipped with their own Space Humid-
ity sensors. A network communications device (MiniLink PD or
CommLink) is needed in order for this feature to operate.
Select YES
for Broadcast Space Humidity. Default is NO.
Confi guration Screen #67 - Broadcast CO
2
VCC-X Cnfg ID #
Broadcast CO2
NO
USE < or > TO CHANGE
The VCC-X can broadcast its CO
2
Reading to other HVAC units
if they are not equipped with their own CO
2
sensors. A network
communications device (MiniLink PD or CommLink) is needed
in order for this feature to operate. Select YES for Broadcast CO
2
.
Default is NO.
Confi guration Screen #68 - Broadcast Building
Pressure
VCC-X Cnfg ID #
Broadcast Build. Pr.
NO
USE < or > TO CHANGE
The VCC-X can broadcast Building Pressure from this unit to any
other unit requiring this value. Select YES for Broadcast Building
Pressure. Default is NO.
Confi guration Screen #69 - Broadcast to Boxes
VCC-X Cnfg ID #
Broadcast to Boxes
NO
USE < or > TO CHANGE
The VCC-X can broadcast all applicable information and commands
to the VAV Boxes. Select YES for Broadcast to Boxes. Default is NO.
Confi guration Screen #70- #73 - Cool/Heat
Stage Delays
VCC-X Cnfg ID #
Cool Stage Delays
Stage Up: 3 Min
Stage Down: 1 Min
VCC-X Cnfg ID #
Cool Stage Delays
Min Run: 5 Min
Min Off: 3 Min
VCC-X Cnfg ID #
Heat Stage Delays
Stage Up: 3 Min
Stage Down: 1 Min
VCC-X Cnfg ID #
Heat Stage Delays
Min Run: 5 Min
Min Off: 1 Min
Both the Heating Stages and the DX Cooling Stages utilize Staging
Up and Down Delay Periods between stages and Minimum Run
Times and Off Times.
VCC-X Confi guration Screens