Connecting Control Builder Section 3 Configuration
152 3BSE036351-510 A
Connecting Control Builder
The Control Builder is installed in a PC that is normally connected to the AC 800M
Controller via the Control Network and the CN1 or CN2 ports on the controller
(see Figure 53 on page 153).
Alternatively, the Control Builder may be connected via the COM4 port (RS-232C)
on the AC 800M Controller. Use the tool cable TK212 and a serial port on the PC.
In redundant configuration, the Control Builder is connected to the Primary CPU
COM4 port. The Backup CPU cannot communicate with Control Builder.
PM851/PM851A is restricted to one Ethernet (CN1) port, thus redundant
Ethernet is not available.
Control Builder as standard does not support CI862. If CI862 is to be used
suitable system extension must be installed.
To use the FF HI functionality, upgrade the firmware of CI852 unit by using
Serial Firmware Upgrade Tool. The Serial Firmware Upgrade Tool loads the
special firmware with FF HI functionality to the Controller. Manually browse the
folder, ..\FirmwareFiles\SC860rFFHI in the Serial Firmware Upgrade Tool and
select firmware.ext.