6.2.3.7 State LEDs
LED State Color LED = OFF LED = ON
Inputs I0...I1 Digital input Yellow Input is OFF Input is ON
Outputs O0...O1 Digital output Yellow Output is OFF Output is ON
6.2.3.8 Technical data
The system data of AC500-eCo V3 apply
Ä
Chapter 6.4 “System data AC500-eCo V3”
on page 154
Only additional details are therefore documented below.
Parameter Value
Process supply voltage UP
Connections Terminal 6 for UP (+24 V DC) and ter-
minal 7 for ZP (0 VDC)
Rated value 24 V DC
Current consumption via UP terminal 5 mA + max. 0.5 A per output
Max. ripple 5 %
Inrush current 0.000002 A²s
Protection against reversed voltage Yes
Rated protection fuse for UP Recommended; the outputs must be pro-
tected by an 3 A fast fuse
Current consumption from 24 V DC power supply
at the L+/M terminals of the CPU
Ca. 10 mA
Galvanic isolation Yes, between the input group and the
output group and the rest of the module
Isolated groups 2 groups (1 group for 2 input channels, 1
group for 2 output channels)
Surge-voltage (max.) 35 V DC for 0.5 s
Max. power dissipation within the module 0.7 W
Weight ca. 120 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not
be hindered by cable ducts or other parts
in the switch-gear cabinet.
6.2.3.8.1 Technical data of the digital inputs
Parameter Value
Number of channels per module 2
Distribution of the channels into groups 1 group for 2 channels
Connections of the channels I0 to I1 Terminals 2 to 3
Reference potential for the channels I0 to I1 Terminal 1
Option boards > TA5110-2DI2DOT - Digital input/output module option board