EasyManua.ls Logo

ABB AC500-eCo V3 - Onboard I;Os: Purpose, Functionality, and Wiring

ABB AC500-eCo V3
195 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.1.1.7 Onboard I/Os
The AC500-eCo V3 processor modules have onboard I/Os which provide several functionalities.
According to the CPU type, the number or the functionality of the onboard I/Os can be different.
6.1.1.7.1 Intended purpose
Table 9: Numbers and types of the onboard I/Os
Processor module No. and type of dig-
ital inputs
No. and type of dig-
ital outputs
No. and type of con-
figurable inputs/
outputs
PM5012-T-ETH 6
24 V DC
(one isolation group)
4
0.5 A max., transistor
(one isolation group)
None
PM5012-R-ETH 6
24 V DC
(one isolation group)
4
2 A max., relay
(two isolation groups)
None
PM5032-T-ETH 12
24 V DC
(one isolation group)
8
0.5 A max., transistor
(one isolation group)
2
24 V DC input or
0.5 A max., transistor
output
(one isolation group)
PM5032-R-ETH 12
24 V DC
(one isolation group)
6
2 A max., relay
(two isolation groups)
2
24 V DC input or
0.5 A max., transistor
output
(one isolation group)
PM5052-T-ETH 12
24 V DC
(one isolation group)
8
0.5 A max., transistor
(one isolation group)
2
24 V DC input or
0.5 A max., transistor
output
(one isolation group)
PM5052-R-ETH 12
24 V DC
(one isolation group)
6
2 A max., relay
(two isolation groups)
2
24 V DC input or
0.5 A max., transistor
output
(one isolation group)
Device specifications