Loading...
Processor module No. and type of dig-
ital inputs
No. and type of dig-
ital outputs
No. and type of con-
figurable inputs/
outputs
PM5072-T-2ETH 12
24 V DC
(one isolation group)
8
0.5 A max., transistor
(one isolation group)
2
24 V DC input or
0.5 A max., transistor
output
(one isolation group)
PM5072-T-2ETHW 12
24 V DC
(one isolation group)
8
0.5 A max., transistor
(one isolation group)
2
24 V DC input or
0.5 A max., transistor
output
(one isolation group)
6.1.1.7.2 Functionality
Parameter Value
PM5012-T-ETH PM5012-R-ETH PM5032-T-ETH
PM5052-T-ETH
PM5072-
T-2ETH(W)
PM5032-R-ETH
PM5052-R-ETH
Digital inputs 6 12
Functionality of
digital inputs
(encoder, fast
counter, counter,
interrupt)
6 DI fast input 24 VDC (max. 5
kHz)
usable as
6 DI 24 V DC standard
2 channel 5 kHz encoder with
frequency measurement or
2 channel 5 kHz encoder with
frequency measurement and
with touch/reset using standard
DI or
2 fast counter (5 kHz)
4 DI as interrupt input with 1
dedicated interrupt task and
input information
4 DI fast input 24 VDC (max. 200
kHz)
usable as
4 DI 24 V DC standard or
4 fast counter (100 kHz) or
2 A/B encoder (200 kHz) with
frequency measurement or
2 full A/B encoders 0 and 1 (200
kHz) with frequency measure-
ment and with touch/reset using
standard highspeed (5 kHz) DI
1 full A/B encoder 0 (200 kHz)
with frequency measurement
and optional with touch/reset
using 2 touch/sync inputs with
A/B encoder 0
4 DI fast input 24 V DC (5 kHz)
usable as
4 DI 24 V DC standard or
4 DI as interrupt input with 1
dedicated interrupt task and
input information
4 touch/sync inputs with A/B
encoder 0 or 1
4 standard DI 24 V DC
Digital outputs 4 8 6
Device specifications
Processor modules > PM50xx
2021/06/293ADR010635, 2, en_US76

Table of Contents