EasyManua.ls Logo

ABB AC500-eCo V3 - Page 99

ABB AC500-eCo V3
195 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
PM5012 PM5032 PM5052 PM5072
Cycle time per instructions (minimum) PM5012 PM5032 PM5052 PM5072
Binary 20 ns
Word 50 ns
Floating point 600 ns
Program execution PM5012 PM5032 PM5052 PM5072
Cyclic min. configurable 10 ms 5 ms 2 ms 1 ms
Time-controlled Yes
Multitasking Yes
Interruption Yes
LEDs Power, Error, Run, MC, MOD1, States of I/Os
RUN/STOP button Yes
Protection of the user program by password On request
Usable accessories On request
Data of I/Os PM5012-x-ETH PM5032-x-ETH PM5052-x-ETH PM5072-T-2ETH
Onboard digital inputs
Channels 6
(incl. 2 counter
inputs 5 kHz and
4 interrupts)
12
(incl. 4 fast counter/encoder inputs (100 kHz), 4 counter
inputs (5 kHz), 4 standard inputs)
Signal voltage 24 V DC type 1
Onboard digital outputs
Type of digital
outputs
PM5012-T-ETH:
Transistor
PM5032-T-ETH:
Transistor
PM5052-T-ETH:
Transistor
PM5072-T-2ETH:
Transistor
PM5012-R-ETH:
Relay
PM5032-R-ETH:
Relay
PM5052-R-ETH:
Relay
-
Channels for
transistor version
4
(5 kHz standard
and PWM)
8
(incl. 4 fast outputs for standard or 4 PWM/2 PTO
(100 kHz), 4 standard outputs (5 kHz))
Channels digital
input/output con-
figurable
(valid for both
PLC version
relais or tran-
sistor)
- 2
Relay version:
The DC channels can be used as
1 PTO/2 PWM (100 kHz) or standard
digital inputs/outputs
Transistor version:
The DC channels can only be used
as standard digital inputs/outputs
2
Transistor ver-
sion:
The DC channels
can only be used
as standard dig-
ital inputs/outputs
Rated voltage
transistor
24 V DC
Nominal current
per transistor
channel
0.5 A resistive
Device specifications
Processor modules > PM50xx
2021/06/29 3ADR010635, 2, en_US 99

Table of Contents