Function Block-Specific Error and Status Codes
Table 58: FB-specific error codes
DiagCode State Name State Description and Output Setting
C001 Error 1 B1 S_Button1 was TRUE on FB activation.
Ready = TRUE
Error = TRUE
S_TwoHandOut = FALSE
C002 Error 1 B2 S_Button2 was TRUE on FB activation.
Ready = TRUE
Error = TRUE
S_TwoHandOut = FALSE
C003 Error 1 B1&B2 The signals at S_Button1 and S_Button2 were TRUE on FB activation.
Ready = TRUE
Error = TRUE
S_TwoHandOut = FALSE
C004 Error 2 B1 S_Button1 was FALSE and S_Button 2 was TRUE after 500 ms in state
8005.
Ready = TRUE
Error = TRUE
S_TwoHandOut = FALSE
C005 Error 2 B2 S_Button1 was TRUE and S_Button 2 was FALSE after 500 ms in state
8005.
Ready = TRUE
Error = TRUE
S_TwoHandOut = FALSE
C006 Error 2 B1&B2 S_Button1 was TRUE and S_Button 2 was TRUE after 500 ms in state
8005 or 8006. This state is only possible when the states of the inputs
(S_Button1 and S_Button2) change from divergent to convergent (both
TRUE) simultaneously when the timer elapses (500 ms) at the same cycle.
Ready = TRUE
Error = TRUE
S_TwoHandOut = FALSE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib