Table 59: FB-specific status codes (no error):
DiagCode State Name State Description and Output Setting
0000 Idle The function block is not active (initial state).
Ready = FALSE
Error = FALSE
S_TwoHandOut = FALSE
8000 Buttons Actu-
ated
Both buttons actuated correctly. The safety related output is enabled.
Ready = TRUE
Error = FALSE
S_TwoHandOut = TRUE
8001 Init Function block is active, but in the Init state.
Ready = TRUE
Error = FALSE
S_TwoHandOut = FALSE
8004 Buttons
Released
No Button is actuated.
Ready = TRUE
Error = FALSE
S_TwoHandOut = FALSE
8005 Button 1 Actu-
ated
Only Button 1 is actuated. Start monitoring timer.
Ready = TRUE
Error = FALSE
S_TwoHandOut = FALSE
8006 Button 2 Actu-
ated
Only Button 2 is actuated. Start monitoring timer.
Ready = TRUE
Error = FALSE
S_TwoHandOut = FALSE
8007 Button 2
Released
The safety related output was enabled and is disabled again.
FALSE at both S_Button1 and S_Button2 was not achieved after disabling
the safety related output.
In this state, S_Button1 is TRUE and S_Button2 is FALSE after disabling
the safety related output.
Ready = TRUE
Error = FALSE
S_TwoHandOut = FALSE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017 AC500-S 315