DiagCode State Name State Description and Output Setting
8003 Wait for Reset Safety demand or errors have been detected and are now cleared. Oper-
ator acknowledgment by Reset required.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
8005 Safe Safety function activated.
Ready = TRUE
S_AOPD_Out = FALSE
S_MutingActive = FALSE
Error = FALSE
8011 Muting For-
ward Start
Muting forward, sequence is in starting phase and no safety demand.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
8012 Muting For-
ward Active
Muting forward, sequence is active.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
8112 Muting Back-
ward Active
Muting backward, sequence is active.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
8122 Muting Back-
ward Start
Muting backward, sequence is in starting phase and no safety demand.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = FALSE
Error = FALSE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017 AC500-S 343